Çeviriciler-Transmitter
Drago marka

Çeviricileri-Transmitter - D62T 456000

Universal Transmitter D62T 46000
Sensor Input: Widerstand: Pt 100, Pt 200, Pt 500, Pt 1000, Ni 100, Ni 200, Ni 500, Ni 1000;
Thermocouple: B, E, J, K, L, N, R, S, T, U, W5Re_W26Re, W3Re_W25Re;
KTY, mV and potentiometer measuring
Output: 0 to 20 mA, 4 to 20 mA, 0 to 10 mA, 2 to 10 mA
0 to 5 V, 0 to 10 V, 1 to 5 V, 2 to 10 V
Measurement Ranges: -270 to +2315 °C, according to sensor type
Power Supply: 24 V DC
Features: Protective Separation, Housing width: 6.2 mm

Technical Data
Input
Resistance Thermometer Sensor Measuring range min. Span
Pt100, Pt200, Pt500, Pt1000 -200 °C to +850 °C 50 K
Ni100, Ni200, Ni500, Ni1000 -50 °C to +180 °C 50 K
Measuring error max. < 0.1 K / 0.05 %
Temperature influence < 50 ppm/K
Sensor connection 4-wire, 3-wire, 2-wire
cable resistance < 100 Ohm per wire, manual compensation for 2-wire connection programmable
Sensor current 0.2 mA
Diagnostic function Sensor / wire break, Error signal on output programmable
Semiconductor Sensors Sensortypes Measuring range min. Span
KTY, 66 different types -50 °C to +300 °C 50 K
Measuring error max. < 0.1 K / 0.05 %
Temperature influence < 50 ppm/K
Sensor connection 4-wire, 3-wire, 2-wire
cable resistance < 100 Ohm per wire, manual compensation for 2-wire connection programmable
Sensor current 0.2 mA
Diagnostic function Sensor / wire break, Error signal on output programmable
Thermocouples Sensor min. Span
Type B, E, J, K, L, N, R, S, T, U 50 K
W5Re_W26Re, W3Re_W25Re 50 K
Measuring error max. < 0.3 K / 0.1 %
Temperature influence < 50 ppm/K
Cold junction compensation internal, external, uncompensated, manual setting
Error of Cold junction internal < 1.5 K
Diagnostic function Sensor / wire break, Error signal on output programmable
mV Input Measuring range min. Span
-125 mV to +125 mV
-1000 mV to +1000 mV 50 mV
50 mV
Measuring error max. < 0.1 %
Temperature influence < 50 ppm/K
Diagnostic function Sensor / wire break, Error signal on output programmable
Potentiometer Input Measuring range min. Span
0 % to 100 % 50 %
Measuring error max. < 0.1 %
Temperature influence < 50 ppm/K
potentiometer resistance 200 Ohm to 50 kOhm
Diagnostic function Sensor / wire break, Error signal on output programmable
Output
Current Voltage
Output signal 0 – 20mA, 4 – 20mA, 0 – 10mA, 2 – 10mA 0 – 5V, 0 – 10V, 1 – 5V, 2 – 10V
Load ≤ 12 V (600 Ohm @ 20 mA) ≤ 5 mA (2 kOhm @ 10 V)
Offset < 20 µA < 10 mV
Linear transfer range 0 to 102,5 % (3,8 to 20,5 mA at Output 4 to 20 mA)
Error signal 0 % / 110 % of output range, programmable
Residual ripple < 10 mVrms
General data
Transfer characteristic Rising / falling linearly
Transmission error < 0.1 %
Temperature coefficient 1) < 100 ppm/K
Measurement rate 4 / s
Test voltage 2.5 kV, 50 Hz Input against output against power supply
Working voltage 2)
(basic insulation) 600 V AC/DC for overvoltage category II and contamination class 2 acc. to EN 61010 part 1
Protection against electric shock 2) Protective Separation by reinforced insulation acc. to EN 61010 part 1 up to 300 V AC/DC for overvoltage category II and contamination class 2 between input and output and power supply.
Ambient temperature Operation
Transport and storage -25 °C to +70 °C
-40 °C to +85 °C (-13 to +158 °F)
(-40 to +185 °F)
Power supply 24 V DC 16.8 V to 31.2 V DC, approx. 0.8 W
EMC 3) EN 61326-1
Construction 6.2 mm housing, protection type: IP 20
Weight Approx. 50 g
Average TC in specified operating temperature range
As far as practicable the standards and rules mentioned above are considered by development and production of our devices. In addition the assembly rules for our devices are to be considered by installation in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
Minor deviations possible during interference
Boldface: Factory setting:
Input Pt100, 0 to 100 °C, 4-wire, Output 0 to 20 mA, transfer characteristic rising, error signal 22 mA