Güç Döngü İsolatörleri ( Loop Power Isolator)
Drago marka

Güç döngü izolatörü - DH 1000

Loop-Powered Isolator DH 1000
Input: 0(4) … 20 mA 1- or 2-channel
Output: 0(4) … 20 mA
Voltage drop: < 2,0 V
Features: Pluggable screw clamp terminals, protective separation,
housing width: 12.5 mm

Technical Data
Input
Input signal 0(4) … 20 mA / max. 30 V
Operating current < 20 µA
Voltage drop < 2,0 V
Overload ≤ 100 mA, 30 V
Output
Output signal 0(4) … 20 mA / max. 28 V
Response time Approx. 5 ms at 500 Ohm load
Ripple < 10 mVrms
General Data
Transmission error 0,1 % of final value
Load error 0,03 % of measured value / 100 Ohm load
Temperature coefficient 1) 15 ppm/K of measured value / 100 Ohm load
DH 101X Test voltage 1,5 kV, 50 Hz
DH 102X Test voltage 4 kV, 50 Hz
Working voltage 2)
(Basic Insulation) Up to 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010–1 between all circuits.
Protection against electrical shock 2) Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010–1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperature Operation
Transport and storage –20 °C to +70 °C
–35 °C to +85 °C
EMC 3) EMVG, EN 61326-1
Construction 12.5 mm housing, protection class: IP 20
Weight Approx. 100 g
Average TC in specified operating temperature range
As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
Minor deviations possible during interference