Güç Döngü İsolatörleri ( Loop Power Isolator)
Drago marka

Güç döngü izolatörü - DH 18

Loop-Powered Isolator DH 18
Input: 0(4) … 20 mA 1- and 2-channel versions
Output: 0(4) … 20 mA
Voltage drop: < 3,0 V
Features: Protective separation, housing width: 11.2 mm

Technical Data
Input
Input signal 0(4) … 20 mA
Operating current < 100 µA
Voltage drop < 3,0 V
Overload ≤ 50 mA, 15 V
Output
Output signal 0(4) … 20 mA
Load < 600 Ohm
Response time Approx. 5 ms at 500 Ohm load
Ripple < 10 mVrms
General Data
Transmission error < 0.1 % of final value
Load error < 0.05 % of measured value / 100 Ohm load
Temperature coefficient 1) < 0.004 %/K / 100 Ohm load
Test voltage 2.5 kV, 50 Hz between all circuits
Working voltage 2)
(Basic Insulation) Up to 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010–1 between all circuits.
Protection against electrical shock 2) Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010–1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperature Operation
Transport and storage 0 °C to +55 °C
–25 °C to +80 °C
EMC 3) EN 61326 -1
Construction 11.2 mm housing, protection classt: IP 20
Weight Approx. 50 g
Average TC in specified operating temperature range
As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
Minor deviations possible during interference