Şönt İzolasyon Amfisi
Drago marka

Şönt İzolasyon Amfisi - DS 7200

Shunt Isolation Amplifier DS 7200
Input: 0…±60 mV, 0…±100 mV, 0…±150 mV, 0…±250 mV, 0…±300 mV, 0…±500 mV
Output: 0…±20 mA, 0…±10 mA, 0…±10 V, 0…±5 V, live/dead-zero
Power supply: 20…253 V AC/DC
Features: Pluggable screw clamp terminals, zero/span compensation,
protective separation, housing width: 12.5 mm

Technical Data
Input
Input signals
(terminal/switch selectable)
± 60 mV, ± 100 mV, ± 150 mV, ± 250 mV, ± 300 mV, ± 500 mV
0…60 mV, 0…100 mV, 0…150 mV, 0…250 mV, 0…300 mV, 0…500 mV
Input resistance > 100 kOhm
Input capacitance Approx. 1 nF
Overload ≤ 30 V
Output
Voltage Current
Output signals
(switch selectable) ± 10 V, 0…10 V, 2…10 V
± 5 V, 0…5 V, 1…5 V ± 20 mA, 0…20 mA, 4…20 mA
± 10 mA, 0…10 mA, 2…10 mA
Load ≤ 10 mA (1 kOhm at 10 V) ≤ 12 V (600 Ohm at 20 mA)
Linear transmission range unipolar: –2 … +110 %, bipolar: –110 … +110 %
Ripple < 20 mVrms General data Transmission error 0,1 % of final value Temperature coefficient 2) 100 ppm/K of final value Zero/Span compensation ± 10 % Cut-off frequency (-3 dB) > 10 kHz 1), switchable to < 30 Hz
Test voltage 4 kV, 50 Hz
Input against output against power supply
Working voltage 3)
(Basic Insulation Up to 1000 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 between all circuits.
Protection against electrical shock 3) Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 600 V AC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperature Operation
Transport and storage –20 °C to +70 °C
–35 °C to +85 °C
Power supply 20 … 253 V AC/DC, AC 48…62 Hz, approx. 2 VA
DC approx. 1.0 W
EMC 4) EMVG, EN 61326 -1
Construction 12.5 mm housing, protection class: IP 20
Weight Approx. 100 g
Factory setting, if no other information is given by ordering
Average TC in specified operating temperature range
As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
Minor deviations possible during interference
Bold: Factory setting, if no other information is given by ordering