Transmitter Tekrarlayıcı
Drago marka

Powering and Isolation of 2-wire HART Transmitters

Repeater Power Supply HART D6C 52500
Input: 4…20 mA Energization of 2-wire transmitters
Output: 4…20 mA Bidirectional HART communication
Power supply: 24 V DC
Features: Pull-spring clamps, protective separation, housing width: 6 mm

Technical Data
Input
Input signal 4 … 20 mA modulated with HART signal
Input resistance ≤ 50 Ohm
Transmitter supply voltages Approx. 18 V
Max. supply current 30 mA
Output
Output signal 4 … 20 mA modulated with HART signal
Load 230 Ohm … 600 Ohm
Offset < 20 µA
Linear transmission range –1 … +110 %
Ripple < 10 mVrms
General Data
Transmission error < 0.1 % of final value
Temperature coefficient 1) < 100 ppm/K Cut-off frequency (-3 dB) > 2.5 kHz HART signal
Response time (T10-90) < 0.2 ms
Test voltage 2.5 kV, 50 Hz between all circuits
Working voltage 2)
(Basic Insulation) Up to 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 between all circuits.
Protection against electrical shock 2) Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperature Operation
Transport and storage –25 °C to +70 °C
–40 °C to +85 °C
Power supply 24 V DC, 16.8 V … 31.2 V DC, ca. 1.2 W
EMC 3) EN 61326-1
Construction 6.0 mm housing, protection class: IP 20
Weight Approx. 50 g
Average TC based on the final value in specified operating temperature range
As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
Minor deviations possible during interference